Sign In | Join Free | My pysqlite.org
pysqlite.org
Wuhan Changguang Battery Co., Ltd
Wuhan Chang Guang Battery Co., Ltd ɑ. . . QUALITY IS PRIORITY ONE . . . QUALITY CONTINUUM . . .Ω
Home > OPzV Battery >

High Sfficiency Safe Stationary OPzV 2V Vrla Battery 420Ah 6OPzV420 ABS Case

Wuhan Changguang Battery Co., Ltd
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Wuhan Changguang Battery Co., Ltd
City: Wuhan
Province/State: Hubei
Country/Region: China
Contact Person:
Mr Song_Gao

High Sfficiency Safe Stationary OPzV 2V Vrla Battery 420Ah 6OPzV420 ABS Case

Brand Name : CGB
Model Number : 6OPzV420
Certification : CE/UL/ISO
Place of Origin : China
MOQ : 100 pcs
Price : negotiation
Payment Terms : T/T or L/C
Supply Ability : 50000 pcs per month
Delivery Time : 30 days
Packaging Details : Packed in carton, and then reinforced with pallet or wooden case for outer packing
Product Name : 6OPzV420
Application : Security
Voltage : 2V
Capacity : 420AH
Size Of Battery : 145*206*471mm
Terminal : M8
Weight : 32.5KG
Case : ABS
Contact Now

High Sfficiency Safe Stationary OPzV Battery 2V 420Ah 6OPzV420


Specifications:

Nominal Voltage2V
Nominal Capacity (C20)420Ah (1.80V @ 20℃)
DimensionLength145mm
Width206mm
Height471mm
Total Height506mm
WeightApprox. 32.5 kg
TerminalM8
Internal ResistanceFull charged@20℃: 0.00095 Ohm
Max Charging Current84A

Description:

●Design life is above 18 years in float application and cycle life is above 1400

times in 80% DOD (Depth of Discharge) term;

● New porous PVC-SiO2 separator with low-internal resistance;

● High strength ABS material for container & lid;

● Wide temperature scope of application (-15~45℃);

● Best temperature of application (20±5℃);

● No leaking, safe and reliable;

● Standing or lying down for using, convenient to transport and install;

● High sealed reaction efficiency, little loss of water, no need to add distilled water or electrolyte, simple to use and maintain;

●Tubular positive grids to avoid active material from shedding..


Applications:

● Telecommunications

● Cable Television

● Electric Utility

● Alarm & Security system

● UPS

● Control Equipment

● Medical Equipment

● Railroad Utility

● Photovoltaic System

● Alternative Energy System

● High Power Backup Supply


TECHNICAL FEATURES:

● Combination of suppleness and rigidity for more flexible connections


● Monitor hole designed


● Flexible and convenient installation, slinky outside looking


Maintenance

● In order to assure service life, the batteries should be correctly inspected and

maintained. The maintenance methods of GEL batteries are recommended as follows:


● Monthly Maintenance

Implement the under-mentioned inspection every month:

Keep the battery-room clean.

Measure and record the ambient temperature of the battery-room.

Check each battery’s cleanness; check damage and overheating trace of the

terminal, container and lid.

Measure and record the total voltage and floating current of the battery

system.


● Quarterly Maintenance

Repeat monthly inspection.

Measure and record floating voltage of every on-line battery. If more than two

cells’ voltage is less than 2.18V after temperature adjustment, the batteries

need to be equalization charged. If the problem is still existing after adopting

above-mentioned measures, the batteries need yearly maintenance or even

three years’ maintenance. If all methods are ineffective, please contact us.


● Yearly Maintenance

Repeat quarterly maintenance and inspection.

Check whether connectors are loose or not every year.

Make a discharge test to check with exact load every year, discharging

30-40% of rated capacity.


● Three-year Maintenance

Operation manual for OPzV series

Make a capacity test every year after three years’ operation. If the capacity of

the battery decreases to lower than 80% of rated capacity, the battery should

be replaced.


Operation and Maintenance

● Insufficient Charge

If the floating voltage is not set correctly (too low or not amend according to

temperature), the battery system will in an insufficient charge state for a long

period of time. When the electricity is out, the battery may not be able to work

because the acid is saltilized and the capacity is decreased.


● Over Charge

Please do not neglect the performance of rectify to transfer floating charge to

equalization charge. If the rectify cannot transfer charge modes because of its

wrong performance or no adjustment, the battery system is always in an

equalization charge state. Thus may cause serious problems for battery, such as

water loss, life decrease, heat out of control, deformation, etc.


● Do charge the battery immediately after discharge.

If the battery is put aside without char ge for a long time after discharge, it will

affect the capacity and life of the battery. Because some large size PbSO4 will

create in the negative which are difficult to transfer to active Pb.


Precautions

●Do not move the battery by handing the post or rolling the battery


●Do not leave any metallic tools or co nnectors on the top of the battery.


●Do not charge the battery in a hermeti cally sealed space. Please leave 5 mm-10

mm between the batteries. Please make sure that the battery is well ventilated.



Product Tags:

tubular plate battery

      

2v vrla battery

      
China Customized Inflatable Bumper Ball Game Bubble Adult Grass CE supplier

High Sfficiency Safe Stationary OPzV 2V Vrla Battery 420Ah 6OPzV420 ABS Case Images

Inquiry Cart 0
Send your message to this supplier
 
From:
Enter your email please.
To: Wuhan Changguang Battery Co., Ltd
Subject:
Message:
Characters Remaining: (0/3000)
 

Home| Products| Suppliers| Quality Suppliers| Site Map |About Us |Contact Us |Help |关于我们 |联系我们

Copyright © 2009 - 2018 pysqlite.org. All rights reserved.